Skip to main content
MJ
Md Jony Islam
Last updated: Jun 3, 2026

earth conductor size calculator

Size earth (ground) conductors from fault current and trip time using S = (I·√t)/k. Includes IEC/NEC references, copper/aluminum tables, and examples

Advertisement
Advertisement
A
Sec
Sqmm
Advertisement

earth conductor size calculator

Size earth (ground) conductors from fault current and trip time using S = (I·√t)/k. Includes IEC/NEC references, copper/aluminum tables, and examples

Advertisement

NEC equipment grounding size

To size an earth conductor on IEC basis, consider S = (I) (√t)/k where I = Prospective earth-fault current (A), t = Protective device disconnection time (s) and k = The material constant in the standard. Round it up to the nearest size in the standard and check against.

Formula & Table Summary:

  • IEC: S (mm²) = ( I(A) · √t(s) ) / k
  • Typical k (illustrative): Cu PVC ≈115, Bare Cu ≈143, Al ≈76
  • NEC: Use Table 250.122 → EGC size by OCPD rating
  • Selection: Round up to next standard size; check installation deratings
Sponsored

grounding conductor size

The size of protective earth/ground conductor calculated by the calculator of the Earth Conductor depends on the prospective fault current ( I ), time to automatic disconnection ( t ) and material constant ( k ). According to IEC usage, apply S = (I · sqrt (t)) / k, where S= cross-section (mm 2 ), and k = a function of conductor material and the temperature rise of the insulation. Standard values: k=115 typical for copper PVC-insulated, k=143 bare copper, k=76 aluminum (example only--check by your convention). In the U.S., the NEC provides Table 250.122 to size the Equipment Grounding Conductor (EGC) with respect to the overcurrent device ratings without reference to I or t. Use this calculator to double check designs, and then round up to the next standard size and check against relevant code (IEC 60364-5-54, 250 NEC). Make sure to always take into account the method of Installation, temperature, and correction parameters as per the local regional regulation.

earth conductor size calculator

IEC — Copper (k = 115)
I (kA) t (s) Scalc (mm²) Std (mm²)
5 0.2 19.44 25
10 0.2 38.88 50
10 0.1 27.50 35
20 0.2 77.76 95
NEC — Illustrative Snapshot
OCPD (A) Min Cu EGC
15–20 14 AWG
60 10 AWG
100 8 AWG
200 6 AWG
400 3 AWG
Advertisement

Frequently Asked Questions - earth conductor size calculator:

Use S = (I · √t) / k, where I is fault current, t is disconnection time, and k is a material constant from the standard.
Illustrative values: copper PVC ≈115, bare copper ≈143, aluminum ≈76. Verify with your standard and insulation class.
From short-circuit studies and the protective device’s time-current curve for the fault location.
Yes, select the next standard cross-section and check mechanical/thermal limits and installation conditions.
NEC uses Table 250.122 based on the overcurrent device rating, not the IEC thermal formula.
Yes where permitted; use the correct k and adjust for terminations and code allowances.
k depends on material and permissible temperature rise; choose the appropriate k per insulation and standard.
Bonding jumpers and PEN conductors have additional rules; check your specific standard sections.
For parallel runs, size each in parallel per code rules; NEC and IEC provide specific guidance.
No. Use it as a design aid and confirm final sizes against the applicable code and manufacturer data.
Advertisement
Advertisement
Advertisement