Calculate the VT secondary voltage from the primary voltage or find the required VT ratio for your system. Includes formulas, tables, and examples for easy conversion.

Advertisement
Advertisement
V
V
V.T.R
Advertisement

VT Ratio Calculator

Calculate the VT secondary voltage from the primary voltage or find the required VT ratio for your system. Includes formulas, tables, and examples for easy conversion.

Advertisement

voltage transformer ratio formula

The ratio of the VT is used to denote the process of reducing a high primary voltage down to a standard secondary voltage. Calculate it by the formula: Vs = Vp(Ssec/Pvt) in which Vp is the primary voltage, Pvt is the VT primary rating, and sec is the secondary voltage rating. The proper choice of VT ratio allows safe and proper metering and protection in an electrical system.

Formula & Table Summary:

  • Secondary Voltage: V_s = V_p × (S_sec / P_vt)
  • Required VT Primary: P_vt = V_p × (S_sec / V_s)
  • Primary-Equivalent from Measured Secondary: V_p_eq = V_s × (P_vt / S_sec)
  • Converter Table (Input → Output):

    Input Formula Output
    VT ratio & Primary Voltage V_s = V_p × (S_sec / P_vt) Secondary Voltage
    Primary Voltage & Desired Secondary P_vt = V_p × (S_sec / V_s) Required VT Primary
    Measured Secondary & VT ratio V_p_eq = V_s × (P_vt / S_sec) Primary-Equivalent Voltage
Sponsored

vt primary secondary conversion

Voltage Transformer (VT) ratios reduce high primary voltages to standard secondary voltages (e.g. 110 V or 120 V) to be used in metering and protection. The VT ratio is indicated as Primary / Secondary, e.g. 11 kV / 110 V. To compute secondary voltage, primary voltage multiplied by secondary rating/VT primary rating. The proper ratio of VT is selected to make the measurements correct and in order to prevent overload of metering circuits. The guide will include formulas, converter tables, the sample calculation, low-competition keywords, image metadata, FAQs in the JSON format, and ready TailwindCSS parts to be implemented immediately. The VT ratio calculator enables electrical engineers, technicians and students to compute secondary voltages with safety and accuracy with respect to primary systems.

voltage transformer calculator

Scenario Input Calculation Result
Example A VT 11kV/110V, V_p = 5.5 kV V_s = 5.5 × 110 / 11000 55 V
Example B VT 33kV/110V, V_p = 16.5 kV V_s = 16.5 × 110 / 33000 55 V
Choose VT V_p = 22 kV, desired V_s = 110 V P_vt = 22 × 110 / 110 22 kV recommended
Back-Calc Measured V_s = 100V, VT 11kV/110V V_p_eq = 100 × 11000 / 110 10 kV
Advertisement

Frequently Asked Questions - VT Ratio Calculator:

VT ratio Primary/Secondary shows how primary voltage is stepped down to a standard secondary (e.g., 11kV/110V).
V_s = V_p × (S_sec / P_vt). Example: VT 11kV/110V, V_p 5.5kV → V_s = 55V.
110 V and 120 V.
Pick VT primary ≥ expected max primary voltage and standard secondary (110/120V). Round up to next standard.
V_p = V_s × (P_vt / S_sec).
Depends on metering standard; 110V is common in older systems, 120V in modern circuits.
VT can saturate and give inaccurate readings; never open-circuit secondary under load.
VT ratios are typically whole numbers; fractional secondary voltages arise if primary voltage isn’t exact multiple.
Effective primary = N × voltage; formula applies using effective primary voltage.
Refer to VT manufacturer catalogs; common primaries: 11, 22, 33 kV etc.