Earth Bondhon
Creators
Rojony Khatun Author
Rojony Khatun
CalculatorToolsProjectExpert
Reviewers
Małgorzata Koperska, MD Steven Wooding
Last updated: October 6, 2025

Electrical System Interlocking Diagram for Safe Operation

🇺🇸
English
Default
🇪🇸
Español
Spanish
🇫🇷
Français
French
🇩🇪
Deutsch
German
Single Phase DP MCB

Single Phase DP MCB

Double Pole Miniature Circuit Breaker for single-phase supply

Single Phase Contactor

Single Phase Contactor

Electromagnetic switch designed for controlling single-phase electrical loads

Single Phase On-off Push Switch

Single Phase On-off Push Switch

Push-button switch to turn single-phase devices ON or OFF

Single Phase Motor 1Hp

Single Phase Motor 1Hp

Single-phase electric motor with 1 horsepower

*Please note: These are affiliate links. I may make a commission if you buy the components through these links. I would appreciate your support in this way!

Magnetic Contactor Interlocking

Learn interlocking in electrical systems to prevent simultaneous operation of conflicting circuits, enhancing safety and avoiding equipment damage.

electrical safety interlocking

Interlocking is also done electrically to avoid conflicting operations within circuits. The correct interlock design will prevent the operation of such devices as forward-reverse contactors, star-delta starters, or circuit breakers at the same time, securing the equipment and the operator.

electrical interlock schematic

Interlocking in electrical systems ensures unwarranted or incompatible activities in circuits, particularly within motor control, or transformers/switchgear. Electrical interlocks employ mechanical, electrical, or relay-based means of ensuring that one device can not be used with another that is operating. One typical such application is forward-reverse motor control, in which interlocks are used to ensure that both forward and reverse contactors are not operated simultaneously to avoid short circuits or motor destruction. Star-delta starters, circuit breaker operation, and ATS systems also utilize interlocks when safety is required. Interlock wiring diagrams frequently have series-connected normally closed contacts of other devices to ensure undesired operation. Adequate interlocking provides the safety of equipment, protection of the operator, and eliminates electrical hazards. Testing is done by simulation requests to operate simultaneously and ensuring that the interlock prevents unsafe operations. Interlocking is essential to industrial electrical systems, motor control panels, and high-voltage switchgear.

Work & Installation (Input → Output Summary)

  • Identify conflicting devices in the system (e.g., forward and reverse contactors).
  • Installmechanical, electrical, or relay interlocksto block unsafe simultaneous operation.
  • Wirenormally closed (NC) contacts of one device in series with the coil of the other.
  • Test interlock by attempting simultaneous operation; verify coil does not energize when blocked.
  • Integrate interlocks withstar-delta starters, ATS, or motor control panelsas required.
  • Proper installation prevents short circuits, motor damage, and unsafe electrical conditions.

Testing & Final Adjustments

  • Inspect interlock wiring for correct NC contacts and series connections.
  • Attempt simultaneous operation of conflicting devices; ensure interlock prevents action.
  • Test forward-reverse interlock in motor circuits: only one direction should energize at a time.
  • Test star-delta interlock: the delta contactor should not close before the star contactor opens.
  • Verify ATS interlock: generator and mains supply should not connect simultaneously.
  • Check mechanical interlocks (if used) for smooth operation.
  • Inspect insulation and secure mounting of all relay contacts.
  • Ensure indication lamps show correct status during interlock operation.
  • Perform multiple cycles to confirm reliability.
  • Document wiring, relay contacts, and testing results for maintenance reference.

Frequently Asked Questions - Magnetic Contactor Interlocking:

What is electrical interlocking?

A safety method that prevents simultaneous operation of conflicting devices in a circuit.

Where is interlocking used?

In motor control panels, star-delta starters, ATS, and high-voltage switchgear.

How does forward-reverse motor interlock work?

It prevents both forward and reverse contactors from energizing at the same time.

Can interlocks be mechanical?

Yes, mechanical interlocks physically prevent simultaneous operation.

Are relay interlocks common?

Yes, electrical relays use NC contacts to prevent unsafe operations.

Is interlocking necessary?

Yes, for equipment safety and to prevent electrical hazards.

Can interlocking prevent short circuits?

Yes, by blocking simultaneous conflicting operations.

How to test interlocks?

Attempt simultaneous operation and ensure interlock blocks the unsafe device.

Can interlocks be automated?

Yes, PLCs can implement automatic interlocking for complex systems.

Do interlocks affect normal operation?

No, they only prevent unsafe or conflicting actions while allowing normal function.

Rojony Khatun

Rojony Khatun

CalculatorToolsProject

Rojony Khatun is the creator of a free online tools website designed to simplify everyday and engineering-related calculations for students, professionals, and hobbyists. The platform offers a wide variety of basic and advanced calculators across key categories, including Electrical Calculators, Electronic Calculators, and Time & Date Calculators, helping users solve problems quickly and accurately.